Proctor Ventient SCW-NS PQ Data

Proctor Ventient SCW-NS PQ Data                                                                                 

Fully Open (with filter)
Ventilation Volume (Q)  m³/hrVentilation Volume (Q)  l/s
Length

(mm)

 Ventilation

Open Area

cm²

 

Effective

Open Area

(αA)  cm²

 ⊿P = 12Pa⊿P = 12Pa
 500 65.020.7 34.4 30.5  (⊿P/9.8) 0.59 9.6 8.5  (⊿P/9.8) 0.59
60086.026.844.139.4  (⊿P/9.8) 0.5612.310.9  (⊿P/9.8) 0.56
700108.032.854.1 48.3  (⊿P/9.8) 0.5615.013.4  (⊿P/9.8) 0.56
800130.038.864.0 57.1  (⊿P/9.8) 0.5617.815.9  (⊿P/9.8) 0.56
900151.044.873.966.0  (⊿P/9.8) 0.5620.518.3  (⊿P/9.8) 0.56
1,000173.050.883.9 74.9  (⊿P/9.8) 0.5623.320.8  (⊿P/9.8) 0.56
1,100194.056.993.283.8  (⊿P/9.8) 0.5325.9 23.3  (⊿P/9.8) 0.53
1,200216.062.9103.192.6  (⊿P/9.8) 0.5328.6 25.7  (⊿P/9.8) 0.53
1,300238.068.9113.0 101.5  (⊿P/9.8) 0.5331.428.2  (⊿P/9.8) 0.53
1,400259.074.9122.9 110.4  (⊿P/9.8) 0.5334.130.7  (⊿P/9.8) 0.53
1,500259.081.0132.7 119.2  (⊿P/9.8) 0.5336.933.1  (⊿P/9.8) 0.53
Fully Open (without filter)
Ventilation Volume (Q)  m³/hrVentilation Volume (Q)  l/s
Length

(mm)

Ventilation

Open Area

cm²

Effective

Open Area

(αA)  cm²

 ⊿P = 12Pa ⊿P = 12Pa
 500 65.023.238.134.1  (⊿P/9.8) 0.56 10.6 9.5  (⊿P/9.8) 0.56
60086.029.047.842.7  (⊿P/9.8) 0.5613.3 11.9  (⊿P/9.8) 0.56
700108.034.957.5 51.3  (⊿P/9.8) 0.5616.014.3  (⊿P/9.8) 0.56
800130.040.866.860.0  (⊿P/9.8) 0.5318.516.7  (⊿P/9.8) 0.53
900151.046.776.4 68.6  (⊿P/9.8) 0.5321.2 19.1  (⊿P/9.8) 0.53
1,000173.052.586.0 77.3  (⊿P/9.8) 0.5323.9 21.5  (⊿P/9.8) 0.53
1,100194.058.495.685.9  (⊿P/9.8) 0.5326.6 23.9  (⊿P/9.8) 0.53
1,200216.064.3105.2 94.5  (⊿P/9.8) 0.5329.226.3  (⊿P/9.8) 0.53
1,300238.070.2114.2103.2  (⊿P/9.8) 0.5031.728.7  (⊿P/9.8) 0.50
1,400259.076.0123.7111.8  (⊿P/9.8) 0.5034.431.1  (⊿P/9.8) 0.50
1,500259.081.9133.3120.5  (⊿P/9.8) 0.5037.033.5  (⊿P/9.8) 0.50

NOTES

Please contact PGA for air flow data when the Ventient SCW-NS is in the 33% open position or if another filter type is required. The position with the curtain wall or window will impact on air flow performance depending on the air flow pathway, the inclusion of acoustic treatment, intumescent fire barrier materials, exterior ember and insect screens and constant air flow dampening. This data may be available. Effective open area (αA) is calculated in house in Japan using apparatus conforming to JISC 9603.

The use of local air cleaning devices in a room can reduce minimum outdoor air requirements (as per AS1668.2 Appendix D) thus reducing required outdoor air quantities via the trickle vent.

Seek advice from gas appliance suppliers regarding use of open flued appliances in any enclosures subject to negative pressures. Advice relating specifically to health care circumstances should be sought for applications intended for health care facilities. Please consult the user guide for instructions on filter access and maintenance.

Where there are specific noise and  vibration isolation requirements, seek advice from an acoustic and vibration consultant. Further data is available.

The designer must consider the position of the openings with respect to contamination, wind effects and uniformity of distribution as out lined in AS1668.2