Proctor Ventient EcoSmart Breathe PQ Data

Proctor Ventient EcoSmart Breathe PQ Data                                                                                 

  

Ventient EcoSmart Breathe Fully Open with filter

 

Ventilation Volume (Q)  m³/hrVentilation Volume (Q)  l/s

Length

(L1)

 Ventilation

Open Area

cm²

Effective

Open Area

(αA)  cm²

 ⊿P = 12Pa

Friction Loss Curve Q= 

  

⊿P = 12Pa

Friction Loss Curve Q=

 

 50025.29.615.513.7 (⊿P/9.8) 0.604.33.8 (⊿P/9.8) 0.60
600 30.511.618.716.6 (⊿P/9.8) 0.605.24.6 (⊿P/9.8) 0.60
700 35.813.621.919.4 (⊿P/9.8) 0.606.15.4 (⊿P/9.8) 0.60
800 41.115.625.222.3 (⊿P/9.8) 0.607.06.2 (⊿P/9.8) 0.60
900 46.417.628.325.1 (⊿P/9.8) 0.607.97.0 (⊿P/9.8) 0.60
1,000 51.719.631.628.0 (⊿P/9.8) 0.608.87.8 (⊿P/9.8) 0.60
1,100 57.021.735.031.0 (⊿P/9.8) 0.609.78.6 (⊿P/9.8) 0.60
1,200 62.323.738.333.9 (⊿P/9.8) 0.6010.69.4 (⊿P/9.8) 0.60
1,300 67.625.741.436.7 (⊿P/9.8) 0.6011.510.2 (⊿P/9.8) 0.60
1,40072.927.744.739.6 (⊿P/9.8) 0.6012.411.0 (⊿P/9.8) 0.60
1,50078.229.747.942.4 (⊿P/9.8) 0.6013.311.8 (⊿P/9.8) 0.60
       
  

Ventient EcoSmart Breathe Fully Open without filter

 Ventilation Volume (Q)  m³/hrVentilation Volume (Q)  l/s

Length

(L1)

Ventilation

Open Area

cm²

Effective

Open Area

(αA)  cm²

 ⊿P = 12Pa Friction Loss Curve Q=  ⊿P = 12PaFriction Loss Curve Q=  
 50025.211.1 15.9  (⊿P/9.8) 0.56 5.0 4.4  (⊿P/9.8) 0.60
600 30.513.4 19.1  (⊿P/9.8) 0.56 6.0  5.3  (⊿P/9.8) 0.60
700 35.815.8  22.6  (⊿P/9.8) 0.567.1 6.3  (⊿P/9.8) 0.60
800 41.118.1 25.9  (⊿P/9.8) 0.53 8.17.2  (⊿P/9.8) 0.60
900 46.420.4  29.1  (⊿P/9.8) 0.539.1  8.1  (⊿P/9.8) 0.60
1,000 51.722.7  32.4  (⊿P/9.8) 0.5310.2  9.0  (⊿P/9.8) 0.60
1,100 57.025.1 35.9  (⊿P/9.8) 0.53 11.3  10.0  (⊿P/9.8) 0.60
1,200 62.327.4  39.1  (⊿P/9.8) 0.5312.3 10.9  (⊿P/9.8)  0.60
1,30067.629.7 42.4  (⊿P/9.8) 0.5013.311.8  (⊿P/9.8) 0.60
1,40072.932.1 45.9  (⊿P/9.8) 0.5014.412.8  (⊿P/9.8) 0.60
1,50078.234.4 49.1  (⊿P/9.8) 0.5015.413.6  (⊿P/9.8) 0.60

NOTES

Please contact PGA for air flow data when the Ventient EcoSmart Breathe is in the 33% open position or if another filter type is required. The addition of interior and exterior covers will impact on air flow performance depending on the inclusion of acoustic treatment, intumescent fire barrier materials and exterior ember and insect screens. This data may be available.

Effective open area (αA) is calculated in house in Japan using apparatus conforming to JIS C9603.

The use of local air cleaning devices in a room can reduce minimum outdoor air requirements (as per AS1668.2 Appendix D) thus reducing required outdoor air quantities via the trickle vent.

Seek advice from gas appliance suppliers regarding use of open flued appliances in any enclosures subject to negative pressures.

Advice relating specifically to health care circumstances should be sought for applications intended for health care facilities.

Please consult the user guide for instructions on filter access and maintenance.

Where there are specific noise and vibration isolation requirements, seek advice from an acoustic and vibration consultant. Further data is available.

The designer must consider the position of the openings with respect to contamination, wind effects and uniformity of distribution as outlined in AS1668.2